Quick question for someone who owns this unit
If you hook up your vacuum gauge directly off the unit with all the other caps on, should it pull down to 50 microns or below rather quickly like I think it should?
Testing a unit I bought on Fleabay which the unit looks barely used but came with some mystery oil. I have run the unit through several purge cycles but still cannot get it below 5000 microns. All the seals are in the original Appion caps.
Fresh oil getting a little cloudy in short order which makes me think there are still contaminates in the unit.
Sent from my SM-N910W8 using Tapatalk